称重传感器

称重传感器
称重传感器

产品类别

联系方式

电话:0755-26738591

传真:0755-26998440

网址:http://www.octsources.com

邮箱:sales@octsources.com

地址:深圳市南山区南头街道虹步路39号马家龙14栋大习科创大厦

产品类别 > 隔离器/转换器 > MVTR-300电压传感器

MVTR-300电压传感器

所属品牌:美国 OSI 来源:深圳市现代豪方仪器仪表点击:472次发布时间:2021-09-27

MVTR-300电压传感器


品牌:美国 OSI

型号:MVTR

类型:均方根电压传感器

双线环路供电,真有效值





特征/FEATURES

•即使在非正弦波形中,也能提供与测量电压成比例的完全隔离的4-20mA输出

•薄型外形允许最大限度地利用控制机柜空间

•嵌入式端子提供更高的安全性

•UL94V-0聚酰胺DIN安装外壳样式

•Provides a fully-isolated 4-20mA output proportional to the measured voltage even in non-sinusoidal waveforms.

•Slim profi le allows maximum use of control enclosure space.

•Recessed terminals provide increased safety.

•UL94V-0 polyamide DIN-mount case style.



应用/APPLICATIONS

•用于准确感应单相和三相装置中电压的真有效值传感器

•非常适合非正弦应用,如VFD和SCR控制负载

•专为工业环境设计

•True RMS transducer for accurately sensing voltage in single- and 3-phase installations.

•Ideal for non-sinusoidal applications, such as VFDs and SCR-controlled loads.

•Designed for industrial environments.









参数

电压输入

0-600Vac

输出

4-20mAdc回路

准确性

±0.25% FS

频率

50-400Hz

测量

交流电

系统配置

1Ø

 

 

输入

交流电压

标准输出型号MVTR

4-20mAdc

0-150

150E2

0-300

300E2

*0-600

*S600E2

 

*注:600Vac型号配有电压互感器(PT)

 



规格

输入INPUT

电压

0-600Vac

频率范围

标准

50-400Hz

负重

150Vac型号

1.0VA

300Vac、600Vac型号

2.0VA

输出OUTPUT

缩放比例

0-F.S.输入=4-20mAdc输出

响应(至90%)

150和300V型号

200毫秒

600V型号

500毫秒

加载

(@24Vdc仪表电源)

0-500Ω

设定点调整

±5%,最小值

介电测试DIELECTRIC TEST

输入/输出

2200Vac

仪表功率INSTRUMENT POWER

环路供电

名义变量

24Vdc

射程

15-35Vdc

精度(包括线性和设定点的影响)

ACCURACY (Includes effects of linearity and setpoint)

60Hz

10-100% F.S.

±0.25% F.S.

所有其他

±1.0% F.S.

输出纹波

<1.0% pk-pk

温度TEMPERATURE

工作范围

-20℃ ~ 60℃

影响

±1.0% F.S.

物理性能PHYSICAL

终端线尺寸

22至12 AWG

重量

150Vac、300Vac型号

0.25磅

带PT的600Vac型号

0.90磅

该装置可安装在

轨道EN50035(DIN 1)或

轨道EN50022(DIN 3)










连接和尺寸


































安装/操作/保修/INSTALLATION / OPERATION / WARRANTY

 

 

 

安装说明/INSTALLATION INSTRUCTIONS

1.只能由合格的电工进行安装!

2.在进行任何电气连接之前,确保电气服务已断开。

3.支路保护按国家和地方规范要求设置检查机构的报告。

4.按要求布线,并按照本表和装置上的接线图固定到端子上。

5.传感器适合安装在600Vac线路上。

6.为防止与带电电路接触,当安装在裸母线上时,要求传感器安装在需要使用工具进入的外壳中。当安装在绝缘电缆上时不需要第二个外壳的电缆。

1. Installation should be performed by qualifi ed electricians only!

2. Make sure electrical service is disconnected before making any electrical connections.

3. Branch circuit protection is required to be provided in accordance with the National and Local codes of the inspection authority.

4. Route wires as required and secure to terminals per connection diagram on this sheet and on the unit.

5. Transducers are suitable for installation on 600Vac lines.

6. To prevent contact with live circuits, when installed on a bare bus bar, the transducer is required to be mounted in an enclosure that requires the use of a tool for access. When installed on an insulated cable this second enclosure is not required.

 

 

操作说明/OPERATING INSTRUCTIONS

1.本装置适用于海拔2000米以下的室内使用。

2.根据安装类别(过电压)II,污染等级2的瞬态过电压。

3.如果需要清洁外表面,则应断电所有供应服务(两个测量和仪表电源电路),并用软刷刷洗或用低压空气吹扫。使用适当的眼部保护。不适合清洗软管。

4.最高相对湿度80%,温度最高31ºC,线性下降至50% 40℃时的相对湿度。

5.最大工作温度范围为-20°C至60°C。

1. This unit is intended for indoor use at altitudes up to 2000 meters.

2. Transient overvoltages according to Installation Category (overvoltage) II, Pollution Degree 2.

3. If cleaning of the exterior surface is necessary, de-energize all services of supply (both measuring and instrument power circuits) and brush with a soft brush or blow off with low-pressure air. Use appropriate eye protection. Not suitable for hose-down cleaning.

4. Maximum relative humidity 80 percent for temperatures up to 31ºC decreasing linearly to 50 percent relative humidity at 40ºC.

5. Maximum operating temperature range is -20°C to 60°C.